With the high-performance differential pressure transmitter with compact and robust Stainless steel electronics housing, the calibration / programming can be done very easy without test pressure by using the Unique One Touch programming button together with the Graphic display with backlight. The multilingual graphic display can indicate a number of chosen engineering units including the process temperature as well as the mA output in a bar graph. Damping times can be adjusted and a 4-20 mA current simulation can be performed. For flow measurement a square root function is built-in with adjustable cut off point.
TECHNICAL DATA
MEASURING RANGE MIN. MAX. | 10 MBAR…20 BAR |
---|---|
STATIC PRESSURE | MAX. 160 BAR OPTION 250 BAR |
PROCESS TEMPERATURE | -20 °C…+100 °C |
ACCURACY | 0,075 % OPTION 0,065 % |
PROCESS CONNECTIONS | PROCESS CONNECTIONS |
TURN DOWN | MAX. 100:1 |
OUTPUT | 4-20 MA 2-WIRE + HART PROTOCOL (VERSION 7.0), PROFIBUS PA |
ADJUSTMENT | WITH PROGRAMMING BUTTON AND DISPLAY, WITHOUT TEST PRESSURE OR WITH HART |
DISPLAY | MULTILINGUAL, WITH BARGRAPH, BACKLIGHT AND PROCESS TEMPERATURE READING |
POWER SUPPLY | 12 - 36 VDC (EX: 12 - 30 VDC) |
PROTECTION | IP66 (OPTION IP68) |
AMBIENT TEMPERATURE | -20 °C...+70 °C |
DIAPHRAGM MATERIAL | AISI 316L, OPTION HASTELLOY C, TANTALUM OR GOLD PLATED |
WETTED PARTS | AISI 316L, OPTION HASTELLOY C |
MATERIAL SENSOR GASKET | VITON, OPTION PTFE OR NBR |
ELECTRONICS HOUSING | AISI 304, OPTION AISI 316 |
CERTIFICATES/APPROVALS | EXPLOSION SAFETY: ATEX EX-IA AND IECEX EX-IA (OPTIONAL T5 AND T6) |